Name: Long rod suspension insulator
Type: Long rod suspension insulator
Related type: Voltage Range: 11kV~230kV
Standard: IEC standard, ANSI standard, BS standard
Graze colors of insulators: light gray
Mechanical failing load: 20kN, 40kN, 70kN, 90kN, 100kN, 120kN and as per client's request
Material: Fiberglass rod & polymeric material
Advantages: Light weight, small size/volume, easy for transportation and installation
High mechanical strength,Super performance for anti-pollution
It has the feature of light weight, small volume, not easily broken, high mechanical strength, high pollution resistant, good aging resistance, high anti explosive and others.
Application: Overhead lines and transmission lines
Parameter (IEC 61109)
Insulator technical description | Unit | Value |
Rated voltage | kV | 10 |
Specified mechanical load | KN | 70 |
Coupling size | mm | 16 |
Structure height | mm | 420±15 |
Min. electric arc distance | mm | 200 |
Min nominal creepage distance | mm | 480 |
Lightning impluse withstand voltage | KV | 115 |
P.Ffrequency wet withstand voltage(not less than) | kV | 45 |