V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company

Model NO.
3QHJ-Air Fliter-005
Certification
ISO9001, ISO14001, En779, En1822
Pleat Distance
7ppi
Core Components
Filter Efficiency
Warranty of Core Components
Not Available
Machinery Test Report
Provided
Applicable Industries
Manufacturing Plant, Food & Beverage Factory
Transport Package
Standard Export Packing
Specification
610x610x292
Trademark
MicroPure-Compact
Origin
Guangdong, China
Reference Price
$ 18.00 - 37.80

Product Description



Compact Filter

Features
The unique V-bank design enables more area of mini-pleated filtration media being assembled and lower pressuredrop, which results in higher dust holding capacity and longer service life.

Frame:                                      
ABS plastic/ Galvanized Frame

Media:                                                      
Glass fiber paper or synthetic fiber paper

Separator:            
Hot melt adhesive


Sealant:        
Polyurethane

Working condition:                                                                            
Continuous Operating Temperature: ≤ 70ºC ,  Humidity: ≤ 80% RH

Recommended Final resistance :                                          
F6 ~ F9 ≤ 350 Pa, H11 ~ H12 ≤ 600Pa, H13 ~ H14 ≤ 650Pa

Efficiency:                                                          
M6(EN 779):60%- 80%@0.3μm, F7(EN 779):80%- 90%@0.3μm
F8(EN 779):90%- 95%@0.3μm, F9(EN 779):≥ 95%@0.3μm
E11(EN1822): ≥ 99% at 0.3μm @0.45m/s   E12(EN1822): ≥ 99.7% at 0.3μm @0.45m/s
H13(EN1822): ≥ 99.97% at 0.3μm @0.45m/s

Application:                                                                                                                                                                                                                 
V-bank filters are designed for high volume airflow requested  facilities. They are mainly used as secondary filters for  facilities with HEPA/ULPA requirements, for instance office  building, clean room and breeding plants, etc.

4V Medium V bank
Dimensions Width ( mm) Height ( mm) Depth ( mm) Media  Area ( m2) Airflow / Pressure  Drop ( m3/h / Pa) Efficiency EN779 Volume ( m3 ) Weight ( kg)
4V-24x24x12 592 592 292 14.3 3600 / 80 F6 0.1 5.0
4V-24x20x12 592 490 292 11.3 2900 / 80 F6 0.08 4.0
4V-24x12x12 592 287 292 6.8 1800 / 85 F6 0.05 3.0
4V-24x24x12 592 592 292 14.3 3600 / 100 F7 0.1 5.0
4V-24x20x12 592 490 292 11.3 2900 / 100 F7 0.08 4.0
4V-24x12x12 592 287 292 6.8 1800 / 105 F7 0.05 3.0
4V-24x24x12 592 592 292 14.3 3600 / 125 F8 0.1 5.0
4V-24x20x12 592 490 292 11.3 2900 / 130 F8 0.08 4.0
4V-24x12x12 592 287 292 6.8 1800 / 135 F8 0.05 3.0
4V-24x24x12 592 592 292 14.3 3600 / 155 F9 0.1 5.0
4V-24x20x12 592 490 292 11.3 2900 / 165 F9 0.08 4.0
4V-24x12x12 592 287 292 6.8 1800 / 170 F9 0.05 3.0

2V Medium V bank
Dimension Width ( mm) Height ( mm) Depth ( mm) Media  Area ( m2) Airflow / Pressure  Drop ( m3/h / Pa) Efficiency EN779 Volume ( m3) Weight ( kg)
2V-24x24x12 592 592 292 9.6 3400 / 65 F6 0.1 3.3
2V-24x20x12 592 490 292          
2V-24x12x12 592 287 292 4.2 1700 / 80 F6 0.05 2.1
2V-24x24x12 592 592 292 9.6 3400 / 100 F7 0.1 3.3
2V-24x20x12 592 490 292          
2V-24x12x12 592 287 292 4.2 1700 / 120 F7 0.05 2.1
2V-24x24x12 592 592 292 9.6 3400 / 130 F8 0.1 3.3
2V-24x20x12 592 490 292          
2V-24x12x12 592 287 292 4.2 1700 / 150 F8 0.05 2.1
2V-24x24x12 592 592 292 9.6 3400 / 160 F9 0.1 3.3
2V-24x20x12 592 490 292          
2V-24x12x12 592 287 292 4.2 1700 / 180 F9 0.05 2.1

4V HEPA V bank
Dimension Width ( mm) Height ( mm) Depth ( mm) Media  Area ( m2) Airflow / Pressure  Drop ( m3/h / Pa) Efficiency EN1822 Volume ( m3) Weight
( kg )
4V-24x24x12 592 592 292 18.5 3400 / 230 E10 0.1 5.0
4V-24x20x12 592 490 292 15.2 2650 / 230 E10 0.08 4.0
4V-24x12x12 592 287 292 8.4 1700 / 230 E10 0.05 3.0
4V-24x24x12-0P 592 592 292 31.6 3000 / 250 E12 0.1 5.0
4V-24x20x12-0P 592 490 292 26.7 2400 / 250 E12 0.08 4.0
4V-24x12x12-0P 592 287 292 14.7 1350 / 250 E12 0.05 3.0

4V HEPA V bank
Dimension Width ( mm) Height ( mm) Depth ( mm) Media  Area ( m2) Airflow / Pressure  Drop ( m3/h / Pa) Efficiency EN1822 Volume ( m3) Weight ( kg)
4V-24x24x12-0P 592 592 292 29.7 3000 / 250 H13 0.1 5.0
4V-24x20x12-0P 592 490 292 24.3 2450 / 250 H13 0.08 4.0
4V-24x12x12-0P 592 287 292 13.7 1350 / 250 H13 0.05 3.0


Various V-section HEPA V bank
Dimension Width ( mm) Height ( mm) Depth ( mm) Media  Area ( m2) Airflow / Pressure  Drop ( m3/h / Pa) Efficiency EN1822 Volume ( m3) Weight ( kg)
5V-24x24x12-0P 610 610 292 45.0 3400 / 250 H13 0.11 20.0
2V-12x24x12-0P 305 610 292 18.0 1700 / 250 H13 0.05 13.0
5V-24x24x12-0P 610 610 292 46.0 3000 / 250 H14 0.11 23.0
2V-12x24x12-0P 305 610 292 18.0 1500 / 250 H14 0.11 20.0
V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company V-Bank Compact HEPA Air Filter HEPA Filter for Pharmaceutical Company