An off-grid solar system permits electricity to be harnessed by solar panels and stored inside a battery without direct connection to the utility grid, providing an independent power supply to your home or business.
Basically, an off-grid solar system is a novel innovation which provides you independent energy harnessed by the sun. An off-grid solar system is made up of the following components.
LSS-52.8KW Off-grid Photovoltaic LiFePO4 Storage Power Supply System | |||||
Item | No. | Description | Unit | Qty | Remark |
Photovoltaic system | 1 | MONO solar panel 550W/41.6V | Pc | 96 | 12S8P |
2 | Bracket | Set | 1 | Tailor-made | |
3 | M4C connectors | Pair | 96 | ||
4 | PV cables PV1-F 1x4.0 | m | 1000 | Panel-Panel-PV combiner | |
Control & Invertor system | 5 | Inverter LSI384-100KVA3 | Pc | 1 | AC380V/220V/50HZ, full load 80KW, with grid power bypass, diesel generator dry contact |
6 | MPPT controller LSM384-100A | Pc | 2 | 1 PV track input 100A, functioning range 420V-800V | |
7 | SPD PV combiner box LSB4B | Pc | 2 | 4 IN 1 OUT, Max. 1000V | |
8 | AC distribution box | Pc | 1 |
Tailor-made, 1*3 Phase in,
1*3 Phase out, with SPD |
|
9 | Cable BVR 16mm² | m | 200 | PV Combiner-controller | |
10 | AC cable YJV4*35*1*16 | m | 10 | Inverter-AC distribution box | |
Lithium Battery System | 11 | LiFePO4 battery LBP384-840AH | Set | 1 | including BMS\LiFePO4 Battery rack\HV system cabinet\ battery connecting cables, communication cables,322KWh |
12 | Cable BVR70 | m | 30 | LiFePO4 battery-Controller, Controller-Inverter | |
13 | Packing, Accessories, Installation tools | Set | 1 |
Rated power(KVA3) |
LSI
10/15/20/30 KVA3 |
LSI
40/50/60 KVA3 |
LSI
80/100/120 KVA3 |
Rated DC
voltage(VDC) |
220/360/384 | 220/360/384 | 360/384 |
Phase | Three phases+N+G | ||
Nominal voltage | 380V AC/400V AC | ||
Nominal frequency | 50/60 Hz | ||
Frequency stability:
when out of sync |
< ± 0.05% | ||
Frequency stability:
when synchronized |
< ± 5% | ||
Current peak factor | 3:1 | ||
Output waveform | Pure sine wave | ||
THD | Liner load <3%; Non-liner load <5% | ||
Dynamic load
voltage transients (from 0 to 100%) |
< ± 5% | ||
Load voltage | <±3%(Balanced Load); <±5%(unbalanced load) | ||
Overload capacity | 125% 10 min, 150% 1 min | ||
Inverter efficiency,
load 100% |
>92% | ||
Computer communication
interface |
RS232 (485 Network remote monitoring Optional) | ||
Operating temperature | 0~40 ºC | ||
Relative Humidity
(No condensation) |
20%~90% | ||
Altitude | ≤5000 (above 1000 mters, rated power derating 1% every 100 meters) | ||
Cooling | Forced cool air | ||
Noise dB | 45~65 (1m from the machine) | ||
Color | Black(Optional) | ||
Weight (kg) | 190-340 | ||
Dimension
(W*D*H,mm) |
600*600*1600 | ||
The above data are for reference only and are subject to change without prior notice. Special voltage can be customized. |