AC SPD FV50B/3-320 is for low-voltage power supply 320V AC, Iimp50kA, 3poles.
1.surge protector Characteristic for surge arrester FV50B/3-320
-
Surge arrester
with compact construction design,
-Used in the lightning protection zones concept at boundary LPZ0B-LPZ1,
-The core parts are spark gap with high discharge capacity,
-35mm2 DIN-rail in accordance with EN 50022/DIN46277-3,
-Low residual voltage and quick response.
-Protection mode: L1, L2, L3-PE
2.Dimension of surge arrester
FV50B/3-320
Why choose us
FATECH ELECTRONIC CO., LTD., is located in Guangdong Provincial New Light Production Base, CHINA, which is a professional manufacturer on R&D and producing on surge protection products. Our company gathered all kinds of high-skillled personnels, including authority technical experts and professionals, and excellent technicians with more than 10 years experience. In-house testing lab. guarantee out-going products quality. Products are certified with TUV, CE; UL pending, 90% material are UL approved.
Our in-house test lab.:We established an independent testing laboratory, including reliability testing laboratory, environmental aging testing laboratory, release testing laboratory, which can be performed tests below:
Impulse current generator (8/20 μS/160kA and 10/350μS/20kA)
Thermal stability tester
Salt Spray Chamber
Multi-function Varistor Tester
On-line Aging Tester
Dielectric Voltage Withstand Tester
1.2/50 Voltage Impulse Generator
Environment Stimulating Tester
Lightning Surge Counter Tester
Our global partners:
We are now exporting more than 100 countries and areas, mainly in Europe, Asia, Latin-America, and Middle East. Our global partner including
Ericsson
Sri Lanka Telecom
Siemens
Our certificates:
3.surge protection device electrical parameters for surge arrester FV50B/3-320
Model No.: FV50B/3-320
|
|
|
|
Max. continuous AC voltage
|
Uc
|
V
|
320
|
Requirement class to DIN EN 61643-1: 2005
|
|
|
Class B
|
Max. Discharge current(8/20μ s)
|
Imax
|
kA
|
140
|
Impulse discharge current (1/350μ s)
|
Iimp
|
kA
|
50
|
Voltage protection level (at In)
|
Up
|
kV
|
<=2.0
|
Response time
|
tA
|
ns
|
100
|
Operation temperature range
|
|
|
-40 ~ +85degree
|
Degree of protection
|
|
|
IP20
|
Remote control contacts
|
|
|
NO
|